Voltage Drop Calculator

Calculate voltage drop and percentage for electrical circuits. Determine proper wire sizing based on length, current, and NEC recommendations. Essential for electrical design and code compliance.

Calculate Voltage Drop

Voltage Drop
0.00 V
Percentage Drop
0.00%
End Voltage
0.00 V
✓ Within NEC 3% recommendation for branch circuits
Calculation:

Quick Reference: Voltage Drop Formulas

DC & AC Single-Phase
VD = (2 × K × I × L) ÷ 1000
K = Ω per 1000 ft, I = Amps, L = Length (ft)
AC Three-Phase
VD = (√3 × K × I × L) ÷ 1000
√3 ≈ 1.732
Voltage Drop Percentage
% Drop = (Voltage Drop ÷ Source Voltage) × 100
NEC recommends ≤ 3% for branch circuits, ≤ 5% total
Published By ChallengeAnswer Editorial Team
Reviewed by
Dr. Snezana Lawrence
Dr. Snezana LawrencePhD in Mathematical History
Dr. Snezana Lawrence

Dr. Snezana Lawrence

Mathematical Historian

15+ years experience

PhD from Yale University. Published mathematical historian ensuring precision in all calculations.

Education

PhD in Mathematical History - Yale University

Mathematical HistoryTime CalculationsMathematical Conversions
View Full Profile

How to Calculate Voltage Drop

Voltage drop is the decrease in electrical potential along a conductor carrying current. Understanding and calculating voltage drop is crucial for electrical system design, ensuring equipment operates efficiently and safely within specified voltage ranges.

Understanding Voltage Drop

When current flows through a wire, the wire's resistance causes a voltage loss. This phenomenon follows Ohm's Law (V = I × R), where the voltage drop equals current times resistance. Longer wires, smaller wire gauges, and higher currents all increase voltage drop.

DC and Single-Phase AC Formula

For DC circuits and single-phase AC circuits, use the following formula:

Voltage Drop (VD) = (2 × K × I × L) ÷ 1000
  • 2 = Multiplier for both supply and return conductors
  • K = Wire resistance in ohms per 1000 feet (at 75°C)
  • I = Load current in amperes
  • L = One-way length of wire run in feet

Example: 12 AWG copper wire (K = 1.98 Ω), 100 feet, 20 amps:
VD = (2 × 1.98 × 20 × 100) ÷ 1000 = 7.92 volts

Three-Phase AC Formula

For three-phase AC circuits, the formula accounts for the phase relationship:

Voltage Drop (VD) = (√3 × K × I × L) ÷ 1000
  • √3 = 1.732, the three-phase factor
  • K = Wire resistance in ohms per 1000 feet
  • I = Load current per phase in amperes
  • L = One-way length of wire run in feet

Example: 6 AWG copper wire (K = 0.491 Ω), 200 feet, 50 amps, 480V:
VD = (1.732 × 0.491 × 50 × 200) ÷ 1000 = 8.50 volts

Calculating Voltage Drop Percentage

Voltage drop is often expressed as a percentage of the source voltage:

Percentage Drop = (Voltage Drop ÷ Source Voltage) × 100

Example: 7.92V drop on a 120V circuit:
% Drop = (7.92 ÷ 120) × 100 = 6.6%

Professional Tip: Always use one-way length in calculations. The formula's multiplier (2 for single-phase, √3 for three-phase) accounts for current flow through both conductors. Measuring round-trip length and using it in the formula will double your calculated voltage drop.

Wire Sizing Table

This comprehensive table shows wire resistance values for copper and aluminum conductors at 75°C. Use these resistance values to calculate voltage drop or select appropriate wire sizes for your electrical installation.

Copper Wire Resistance (75°C)

Wire SizeResistance (Ω/1000 ft)Ampacity (75°C)Typical Use
14 AWG3.1420ALighting circuits, receptacles
12 AWG1.9825AGeneral purpose circuits, appliances
10 AWG1.2435AWater heaters, dryers, air conditioners
8 AWG0.77850AElectric ranges, sub-panels
6 AWG0.49165ALarge appliances, feeders
4 AWG0.30885AService entrance, sub-panels
2 AWG0.194115AService entrance, large feeders
1/0 AWG0.122150AService entrance, main feeders
2/0 AWG0.0967175AService entrance, main feeders
4/0 AWG0.0608230ALarge service entrance
250 kcmil0.0515255ACommercial service entrance
350 kcmil0.0367310ACommercial/industrial feeders
500 kcmil0.0258380ALarge commercial feeders

Aluminum vs. Copper Comparison

Aluminum conductors have higher resistance than copper and require larger wire sizes for equivalent performance:

Copper SizeCopper Ω/1000ftAluminum EquivalentAluminum Ω/1000ft
12 AWG1.9810 AWG2.04
10 AWG1.248 AWG1.28
8 AWG0.7786 AWG0.808
6 AWG0.4914 AWG0.508

Note on Aluminum: When using aluminum conductors, select a wire size two gauges larger than the copper equivalent to achieve similar voltage drop characteristics. Aluminum is lighter and less expensive but requires special connectors and installation techniques to prevent oxidation issues.

NEC Voltage Drop Requirements

The National Electrical Code (NEC) provides recommendations for maximum voltage drop to ensure safe and efficient electrical system operation. While not mandatory requirements, following these guidelines is considered best practice and may be required by local jurisdictions.

NEC Article 210.19(A) - Branch Circuits

The NEC recommends that voltage drop on branch circuits should not exceed:

  • 3%Maximum recommended voltage drop for branch circuits from the panel to the furthest outlet
  • Example: On a 120V circuit, 3% = 3.6V maximum drop
  • Example: On a 240V circuit, 3% = 7.2V maximum drop

NEC Article 215.2(A) - Feeders

For feeder circuits (wires from service entrance to sub-panels):

  • 5%Maximum total voltage drop for combined feeder and branch circuit
  • If branch circuit has 3% drop, feeder should be limited to 2% drop
  • This ensures total system drop remains at or below 5%

Practical Voltage Drop Targets

Excellent (≤ 2%)

  • • Motor circuits and sensitive equipment
  • • Long wire runs
  • • Solar and renewable energy systems
  • • Computer and data center circuits

Acceptable (2-3%)

  • • General purpose branch circuits
  • • Lighting circuits
  • • Receptacle outlets
  • • Typical residential applications

Marginal (3-5%)

  • • May cause equipment issues
  • • Reduced energy efficiency
  • • Consider upsizing wire
  • • Not recommended for motors

Unacceptable (> 5%)

  • • Equipment malfunction likely
  • • Code violation in most jurisdictions
  • • Safety concerns
  • • Must upsize wire or redesign circuit

Special Considerations

Motor Circuits

Motors are particularly sensitive to voltage drop. A 10% voltage reduction can decrease motor life by 50%. Keep motor circuit voltage drop to 2% or less for optimal performance and longevity. Use larger conductors for long motor feeder runs.

LED and Electronic Loads

LED drivers and electronic equipment may be sensitive to voltage variations. While 3% is generally acceptable, some sensitive electronics perform better with lower voltage drop. Check manufacturer specifications for critical equipment.

Utility Voltage Variation

Remember that utility-supplied voltage can vary ±5% from nominal. Combined with system voltage drop, equipment may see voltages significantly different from nameplate ratings. Design systems to accommodate these variations.

Practical Applications

Understanding voltage drop calculations is essential for various electrical installations. Here are common scenarios where voltage drop analysis is critical for system performance and code compliance.

Residential Applications

Example 1: Kitchen Appliance Circuit

Scenario: 20A kitchen circuit, 80 feet from panel, 12 AWG copper wire

Calculation:

VD = (2 × 1.98 × 20 × 80) ÷ 1000 = 6.34V% Drop = (6.34 ÷ 120) × 100 = 5.28%

Solution: Upgrade to 10 AWG (K = 1.24):

VD = (2 × 1.24 × 20 × 80) ÷ 1000 = 3.97V (3.31% - acceptable)

Example 2: Detached Garage Sub-Panel

Scenario: 60A sub-panel, 150 feet from main panel, 240V

Wire Selection: Try 6 AWG copper (K = 0.491)

VD = (2 × 0.491 × 60 × 150) ÷ 1000 = 8.84V% Drop = (8.84 ÷ 240) × 100 = 3.68%

Result: Exceeds 3% recommendation. Upgrade to 4 AWG (K = 0.308):

VD = (2 × 0.308 × 60 × 150) ÷ 1000 = 5.54V (2.31% - excellent)

Commercial and Industrial Applications

Example 3: Three-Phase Motor Circuit

Scenario: 50 HP motor (65A), 480V three-phase, 200 feet from panel

Wire Selection: Try 6 AWG copper (K = 0.491)

VD = (1.732 × 0.491 × 65 × 200) ÷ 1000 = 11.05V% Drop = (11.05 ÷ 480) × 100 = 2.30%

Result: Acceptable for motor circuits (< 3%)

Solar and Renewable Energy

Example 4: Solar Panel DC Circuit

Scenario: Solar array 30A output, 48V DC, 75 feet to charge controller

Wire Selection: Try 10 AWG copper (K = 1.24)

VD = (2 × 1.24 × 30 × 75) ÷ 1000 = 5.58V% Drop = (5.58 ÷ 48) × 100 = 11.63%

Solution: Unacceptable for solar. Upgrade to 6 AWG (K = 0.491):

VD = (2 × 0.491 × 30 × 75) ÷ 1000 = 2.21V (4.60%)

Better, but solar systems target 2%. Use 4 AWG (K = 0.308):

VD = (2 × 0.308 × 30 × 75) ÷ 1000 = 1.39V (2.89% - still high)

Optimal: 2 AWG (K = 0.194):

VD = (2 × 0.194 × 30 × 75) ÷ 1000 = 0.87V (1.81% - excellent for solar)

Design Tip: When voltage drop calculations fall near the 3% threshold, consider upsizing the wire. The cost difference is minimal during installation but prevents future issues and provides capacity for additional loads. This is especially important for permanent installations and critical circuits.

How We Calculate Voltage Drop

Our voltage drop calculator uses industry-standard formulas based on conductor resistance, circuit length, and load current. The calculations follow NEC guidelines and electrical engineering principles to provide accurate results for system design and analysis.

Calculation Methodology

1. Wire Resistance Values

We use standard conductor resistance values from NEC Chapter 9, Table 8. These values are specified at 75°C operating temperature in ohms per 1000 feet:

  • • Copper conductors: 14 AWG through 1000 kcmil
  • • Aluminum conductors: 12 AWG through 1000 kcmil
  • • Values account for DC resistance at 75°C
  • • AC circuits: values approximate resistance (reactance ignored for most applications)

2. Single-Phase Calculation

For DC and single-phase AC circuits:

VD = (2 × K × I × L) ÷ 1000

Where:

  • 2 = Round-trip multiplier (supply and return conductors)
  • K = Conductor resistance (Ω per 1000 feet)
  • I = Load current (amperes)
  • L = One-way conductor length (feet)

3. Three-Phase Calculation

For three-phase AC circuits:

VD = (√3 × K × I × L) ÷ 1000VD = (1.732 × K × I × L) ÷ 1000

Where:

  • √3 = 1.732, three-phase factor
  • • Voltage drop is line-to-line
  • • Current is per-phase line current
  • • Assumes balanced three-phase load

4. Percentage Calculation

Voltage drop is expressed as a percentage of source voltage:

% Drop = (Voltage Drop ÷ Source Voltage) × 100

This percentage is compared against NEC recommendations (3% branch, 5% total) to determine circuit acceptability.

5. End Voltage

The voltage available at the load:

End Voltage = Source Voltage - Voltage Drop

This is the actual voltage that will be delivered to the connected equipment.

Assumptions and Limitations

Our calculations make the following assumptions:

  • Conductor temperature: 75°C (167°F) - standard for most THHN/THWN wire
  • AC calculations use DC resistance (valid for power frequencies 50-60 Hz)
  • Three-phase systems are balanced (equal current on all phases)
  • Conduit effects and conductor spacing: minimal impact (typically < 5%)
  • Power factor: not included (affects current magnitude, not voltage drop per amp)
  • Harmonic distortion: not included (may increase effective resistance)

Engineering Note: For critical applications, long runs, or high-frequency loads, consult a licensed electrical engineer. AC circuits with significant reactance, high harmonic content, or skin effect considerations may require more detailed analysis beyond these simplified calculations.

Frequently Asked Questions

What is voltage drop in electrical circuits?

Voltage drop is the reduction in voltage as electrical current flows through wire resistance. It occurs due to the resistance of conductors and increases with wire length, current load, and smaller wire sizes. Excessive voltage drop can cause equipment malfunction and energy waste.

What is the voltage drop formula?

For DC and AC single-phase: VD = (2 × K × I × L) ÷ 1000, where K is wire resistance per 1000 feet, I is current in amps, and L is one-way length in feet. For AC three-phase: VD = (√3 × K × I × L) ÷ 1000. The factor 2 accounts for both supply and return conductors.

What is acceptable voltage drop per NEC?

The NEC recommends maximum 3% voltage drop for branch circuits and 5% total for feeders plus branch circuits combined. For example, on a 120V circuit, 3% equals 3.6V drop, and 5% equals 6V drop. These are recommendations, not mandatory requirements.

How do I calculate voltage drop percentage?

Voltage drop percentage = (Voltage Drop ÷ Source Voltage) × 100. For example, if voltage drop is 3.6V on a 120V circuit: (3.6 ÷ 120) × 100 = 3%. Keep this below NEC recommendations of 3% for branch circuits.

What wire size do I need to reduce voltage drop?

Use larger wire gauge to reduce voltage drop. Each step up (e.g., 12 AWG to 10 AWG) reduces resistance by approximately 37%. Copper has lower resistance than aluminum. Calculate required wire size based on circuit length, current, and acceptable voltage drop percentage.

Does voltage drop affect power consumption?

Yes, voltage drop wastes energy as heat in the conductors and can cause equipment to draw more current to compensate for lower voltage. Motors and other equipment may overheat or fail to operate properly. Reducing voltage drop improves energy efficiency and equipment lifespan.

What is the difference between copper and aluminum wire resistance?

Aluminum has approximately 1.6 times the resistance of copper for the same wire size. For example, 12 AWG copper has 1.98 Ω per 1000 feet, while 12 AWG aluminum has 3.25 Ω per 1000 feet. Use aluminum wire two sizes larger than copper for equivalent performance.

How does wire length affect voltage drop?

Voltage drop increases linearly with wire length. Doubling the length doubles the voltage drop. Always use one-way length (not round-trip) in calculations, as the formula accounts for both supply and return conductors. Long wire runs require larger gauge wire.

Why is voltage drop important for motors?

Motors are sensitive to low voltage. Excessive voltage drop causes motors to draw higher current, overheat, and fail prematurely. A 10% voltage drop can reduce motor life by 50%. Keep voltage drop under 3% for motor circuits to ensure reliable operation and longevity.

Can I use voltage drop calculator for solar panels?

Yes, use DC system type for solar panel calculations. Solar systems are particularly sensitive to voltage drop as it directly reduces power output. Many solar installations target 2% or less voltage drop. Calculate drop for both DC (panels to inverter) and AC (inverter to service panel) circuits.

How do I measure actual voltage drop?

Measure voltage at the source (panel) and at the load (equipment) while the load is operating at full current. The difference is the voltage drop. Use a quality digital multimeter and ensure good contact at measurement points. Compare measured drop to calculated values.

What causes high voltage drop?

High voltage drop is caused by: undersized wire gauge, excessive wire length, high current loads, poor connections, corroded terminals, or damaged conductors. Solutions include using larger wire, reducing circuit length, redistributing loads, or improving connections.

Dr. Snezana Lawrence
Expert Reviewer

Dr. Snezana Lawrence

Mathematical Historian | PhD from Yale

Dr. Lawrence is a published mathematical historian with a PhD from Yale University. She ensures mathematical precision and accuracy in all our calculations, conversions, and academic score calculators. Her expertise spans computational mathematics and educational assessment.

View LinkedIn Profile